Editorial

A feature designed to recover access can end up weakening the entire system. Mitsubishi Electric confirmed that the response used by the security-challenge mechanism in several ICONICS and GENESIS products is fixed and shared by all users. If an attacker obtains that response, the attacker may unlock the system remotely.

The advisory covers four vulnerabilities, but their conditions are different. One requires the attacker to have already logged on locally and to be able to import a file as an administrator. Another requires administrative privileges in the affected product. The recovery flaw, in contrast, can be exploited remotely when the attacker obtains the fixed response. Counting CVEs or assigning a single severity label is therefore insufficient. Each vulnerability must be related to the installed version, available accounts, and the server’s actual exposure.

EPICS Base also deserves attention this week because a network-message processing flaw may cause memory corruption or potential unauthenticated code execution. Nozomi Networks fixed two issues in the Guardian and CMC update mechanism, while Hitachi Energy published actions for its TRO600 routers and the CoreTec technology used for transformer monitoring.


Vulnerabilities of the Week


[CRITICAL] ICONICS and GENESIS: A Fixed Recovery Response Can Unlock the System

The Mitsubishi Electric advisory covers four vulnerabilities in GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI, IoTWorX, MC Works64, GENESIS32, and BizViz. The highest score is 9.4 under CVSS 4.0, but the scope and requirements differ for each vulnerability:

  • CVE-2026-16436: The challenge response used to unlock the system is fixed and shared by all users. A remote attacker who obtains it may bypass authentication.
  • CVE-2026-16437: An administrator with local access may read or modify the file that stores the response.
  • CVE-2026-16438: An affected-product administrator account may launch and operate DCOM objects locally or remotely with permissions that should require UAC elevation.
  • CVE-2023-4863: A flaw in libwebp may allow code execution when a crafted file is imported. This scenario requires the attacker to have logged on locally and to perform the import as a product administrator.

For the three 2026 vulnerabilities, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI 10.97.3 and earlier are affected. The fix is included in ICONICS Suite 10.98 or later. IoTWorX 10.97.3 and earlier should be updated to 10.98 or later, and GENESIS 11.03 and earlier to 11.04 or later. CVE-2023-4863 affects GENESIS64 and ICONICS Suite versions 10.97 through 10.97.2 and was fixed in version 10.97.3.

Mitsubishi Electric does not plan to release fixed versions of MC Works64, GENESIS32, or BizViz. For these product lines, the vendor recommends applying its mitigations and considering migration to GENESIS64 or GENESIS.

View Mitsubishi Electric advisory 2026-006 →

Suggested action: Identify each product and version separately; do not treat the family as a single component. Prioritize servers reachable from other networks and review who can sign in with product-administrator accounts. Update supported product lines and apply the vendor’s mitigation procedure to the file that stores the security response. For products without a planned fix, document compensating controls and a migration path.


[CRITICAL] EPICS Base Network Messages May Cause Memory Corruption and Potential Code Execution

EPICS Base 7.0.10 and earlier contain four vulnerabilities in network-message processing. The most serious, CVE-2026-114595, has a CVSS v3.1 score of 9.8. An integer overflow may result in an incorrect memory allocation. Subsequent processing of attacker-controlled data may cause memory corruption, denial of service, or potential code execution.

The other three vulnerabilities — CVE-2026-114596, CVE-2026-114597, and CVE-2026-114598 — may cause out-of-bounds writes or reads, process instability, information disclosure, or denial of service. Their published vectors require neither credentials nor user interaction.

EPICS is used primarily in accelerators, telescopes, laboratories, and some specialized industrial systems. It may not appear in an inventory organized only by equipment brand because EPICS Base can be embedded in an application or internally developed system.

The EPICS Community released version 7.0.11 with the fixes. CISA reported no known public exploitation at the time of the advisory.

View advisory ICSA-26-300-01 → Download EPICS Base 7.0.11 →

Suggested action: Search for EPICS Base by dependency and version in addition to reviewing the equipment inventory. Identify IOCs and services reachable from other networks, update to 7.0.11, and validate compatibility with older clients during testing. Until the change is complete, restrict access to EPICS protocols to the network segments that need them and monitor for unexpected process crashes or restarts.


[HIGH] Nozomi Guardian and CMC Accepted Update Bundles Manipulated by an Administrator

Nozomi Networks published two vulnerabilities in the Guardian and Central Management Console (CMC) update function. CVE-2026-33923 allows a crafted bundle to pass signature verification and run an unsigned script. CVE-2026-33924 covers two command-injection flaws in the bundle contents. In both cases, the code runs with root privileges.

An attacker needs administrative privileges to supply and install the bundle, so these issues do not provide an unauthenticated initial-access route. They do increase the impact of a compromised administrator account and turn the update channel into a privileged execution path.

Guardian and CMC versions earlier than 26.4.0 are affected. Nozomi recommends updating to version 26.4.0 or later, restricting access to the web management interface, reviewing privileged accounts, and installing bundles only from official sources.

View advisory NN-2026:21-01 → View advisory NN-2026:22-01 →

Suggested action: Verify the version of every Guardian and CMC appliance and review accounts with administrative privileges. Update to version 26.4.0 or later and confirm the origin of previously installed bundles. Restrict the management console to a controlled administrative network.


[HIGH] Hitachi Energy Fixes TRO600 and CoreTec, but the Attack Scenarios Differ

Hitachi Energy TRO600 industrial routers contain two vulnerabilities. CVE-2026-106087 allows an unauthenticated remote attacker to read or download files, including configuration data and passwords. CVE-2026-10756 requires an authenticated account and allows port forwarding to reach services intended to be accessible only from the device itself. This second condition may facilitate additional attacks against internal functions.

Hitachi Energy recommends updating TRO600 to version 9.2.2.1. The 9.1 branch was fixed in version 9.1.2.0, although the vendor recommends moving to the latest release.

The CoreTec advisory covers CVE-2026-13162, an operating-system command-injection flaw, and CVE-2026-43284, the Linux kernel Dirty Frag vulnerability that allows a low-privileged local user to escalate to root. CoreTec is part of Hitachi Energy’s transformer monitoring and digitalization technology; it is not a cybersecurity platform. CoreTec 4 and CoreTec 5 through version 3.4.0 are affected. The specified remediation is to update CoreTec 5 to 5.0.0.

View TRO600 advisory ICSA-26-302-02 → View CoreTec advisory ICSA-26-302-03 →

Suggested action: For TRO600, prioritize devices reachable from untrusted networks and protect configuration files and credentials after updating. For CoreTec, confirm both the version and the local accounts that can access the system. Coordinate the update with the person responsible for transformer monitoring and test data acquisition before returning the equipment to service.

Every update should be validated with the vendor, tested in a controlled environment, and implemented through the organization’s change-management process and approved maintenance windows.


In Brief

  • Mendix SAML: CVE-2026-89209 allows a valid SAML response to be replayed in identity-provider-initiated flows. Mendix 9 should use SAML module 3.6.29 or later; Mendix 10 and 11 should use 4.2.4 or later. As a temporary mitigation, Siemens recommends disabling IdP-initiated sign-on. View SSA-137528 →
  • Legacy ICONICS/Mitsubishi products: No fix is planned for the recovery flaws in MC Works64, GENESIS32, or BizViz. Continuing to operate these products requires compensating controls and a replacement plan.
  • Known exploitation: None of the main advisories in this edition includes confirmation from the vendor or CISA of active exploitation. The proposed priorities are based on exposure, attack requirements, operational impact, and the availability of a fix.

Closing Thoughts

This week’s main finding is not that a historian automatically becomes an entry point. It is that a shared recovery function may weaken the authentication boundary of an entire product family, while other vulnerabilities in the same advisory require local access or prior administrative privileges.

Start with ICONICS and GENESIS instances reachable from other networks and any deployment of EPICS Base 7.0.10 or earlier. Then review Guardian and CMC, particularly where the management console has broad reach. For TRO600 and CoreTec, confirm that the product exists in the inventory before sending the advisory to operations.

Good prioritization means distinguishing a technical capability from a practical attack path. That difference prevents teams from postponing an important correction or interrupting a process because of a scenario that does not apply to their architecture.


The analysis and prioritization expressed in Perímetro are the editorial responsibility of Roberto Manzo. This newsletter does not replace technical advice tailored to your organization.

How protected is your OT network?