A Low-Privilege User Can Execute SQL in PowerSYSTEM Center
PowerSYSTEM Center exposes SQL queries and administrative resources. We also examine critical ABB flaws and a WAGO fix already deployed.

This week, the priority is on platforms that manage substations and automation equipment connected to industrial networks. PowerSYSTEM Center contains two critical vulnerabilities that allow an authenticated user to access administrative resources and execute unauthorized SQL queries. ABB has also published advisories for Netcontrol and Advanced Batch Management. WAGO confirmed that a password recovery flaw has already been fixed centrally, but organizations should still review activity that occurred before the correction.
PowerSYSTEM Center: The Risk Begins With a Low-Privilege Account
Subnet Solutions PowerSYSTEM Center contains two critical vulnerabilities. CVE-2026-63017 allows an authenticated low-privilege user to access resources reserved for administrators. CVE-2026-63774 takes advantage of insufficient input validation in the report designer to execute unauthorized SQL queries.
The attack scenario requires access from an adjacent network and a valid account. This is not an unauthenticated vulnerability that can be exploited directly from the Internet, as the initial draft suggested. Even so, the risk remains significant in an OT network where contractor, engineering, or support accounts can reach the server.
The affected versions are:
- PowerSYSTEM Center 2020 5.29.x and earlier: affected by CVE-2026-63017.
- PowerSYSTEM Center 2024 6.0.x through 6.2.x: affected by both vulnerabilities.
- PowerSYSTEM Center 2026 7.0.x through 7.1.x: affected by both vulnerabilities.
What to do: PowerSYSTEM Center 2020 should receive Update 30. The 2024 and 2026 branches should be upgraded to PowerSYSTEM Center 2026 Update 1.1. If the update cannot be applied immediately, monitor user activity and disable access to the report designer. Also review which low-privilege accounts can reach the server from adjacent segments.
PHP2Shell Reaches ABB Netcontrol Equipment
ABB updated its advisory covering Netcontrol 100, 200, and 500, GW502-iM, and NAM for two critical PHP vulnerabilities: CVE-2026-109618 and CVE-2026-109619. Successful exploitation could allow an attacker to insert and execute arbitrary code on an affected product.
The important point is not simply that a device “uses PHP.” Organizations must confirm the model, installed software package, and the specific correction published by ABB. For Netcon 200 GWDD-A03, ABB released package A103.03.020 on November 2, 2026. Other products covered by the advisory must be matched by exact identifier against the manufacturer’s table.
What to do: identify Netcontrol and NAM equipment in substations, telecontrol gateways, and operation centers. Record the model and version before scheduling changes. For Netcon 200 GWDD-A03, validate package A103.03.020 with ABB or your integrator. For all other models, use only the correction assigned by the manufacturer. While waiting for a maintenance window, restrict access to management interfaces from unauthorized networks and review unexpected connections to the device.
Read ABB cybersecurity advisories
Advanced Batch Management: The Vulnerable Component Is in Node.js
CVE-2026-111497, known as Node2Shell, affects the Brotli decoder included in the Node.js runtime used by ABB Advanced Batch Management 1.0, 1.1, 1.1b, 1.2, and 1.2.1. A crafted Brotli stream may trigger an out-of-bounds write, stop the process, disclose memory, or allow code execution.
ABB states that it did not identify a default path to the vulnerable decoder in the standard configuration it reviewed. The risk increases when a project includes custom HTTP nodes or integrations that download and decompress Brotli responses.
What to do: for ABM 1.2 and 1.2.1, migrate the runtime to Node.js 24.22.1 or later within the 24.x branch. For ABM 1.0, 1.1, and 1.1b, the migration path depends on the Node-RED version: projects using Node-RED 3 must first move to Node-RED 4 before updating Node.js. Test nodes and flows in a controlled environment before restarting production. If an integration cannot yet be updated, prevent automatic decompression of responses containing Content-Encoding: br according to the ABB advisory.
Read ABB advisory 4JNO000550-1189
WAGO Building Cloud Services: No Patch Is Pending, but a Review Is
WAGO reported that Building Cloud Services versions 7.19 through versions earlier than 7.36.156 allowed passwords to be reset without completing email verification. An unauthenticated attacker could establish new credentials for another account and gain access with that user’s permissions.
WAGO corrected the centrally managed service on August 26, 2026, in version 7.36.156. Customers do not need to install an update. The advisory does not report confirmed exploitation.
What to do: review unexpected password changes and anomalous account activity that occurred before the correction date. Pay particular attention to accounts with privileges over buildings, HVAC, energy systems, or facilities managed by third parties. Changing every password without first reviewing the logs may remove useful investigative context.
In Brief
- ABB IPEC iSM Local Server: ABB published patches for installations based on Debian 11, 12, and 13 covering PHP2Shell and NTFS-3G vulnerabilities. Legacy platforms require direct coordination with ABB. The manufacturer recommends applying the corrections as soon as possible and had not reported active exploitation against the product when the advisory was published.
- ABB B&R: the November 9 advisory covers OpenSSL vulnerabilities with a maximum severity score of 9.8 in mapp View, B&R Linux 12, industrial panels and PCs, PVI, and other components. Do not apply a generic update; first match the exact product and version against the ABB matrix.
- Inventory before scanning: for PowerSYSTEM Center and Advanced Batch Management, the decisive information is the application and component version. A scanner that detects only the operating system may not identify the exposure correctly.
Closing Thoughts
This week’s lesson is straightforward: “critical” does not automatically mean “remote and unauthenticated.” PowerSYSTEM Center requires a valid account and adjacent network access, but that condition should not be minimized in networks where integrators and contractors share access. For ABB products, the challenge is identifying the affected product and applying the correct package—not updating individual components in production without coordination.
Share this edition with the teams responsible for substations, telecontrol, batch automation, and building management. If any of these products appear in your inventory, turn the advisory into an assigned task with a confirmed version and a defined maintenance window.
Until next week.
Roberto Manzo
The analysis and prioritization expressed in Perímetro are the editorial responsibility of Roberto Manzo. This newsletter does not replace manufacturer instructions or a technical assessment specific to your organization.